Fire Door Ratings Explained: What -/60/30 and -/120/30 Mean

Fire Door Ratings Explained

Fire door ratings such as -/60/30 and -/120/30 are Fire Resistance Levels (FRL). It tells you how long the complete doorset, meaning the door, frame, seals and hardware together, keeps fire out of the next space. The three numbers are structural adequacy, integrity and insulation, in minutes.

How to read fire door ratings

An FRL is written as three figures separated by slashes: structural adequacy / integrity / insulation. A dash means the criterion does not apply.

  • Structural adequacy is the ability to carry load. Doors do not carry building loads, so this is almost always a dash.
  • Integrity is how long the door stops flames and hot gases passing through. For a -/60/30 door this is 60 minutes.
  • Insulation is how long the unexposed face stays below a set temperature rise. For a -/60/30 door this is 30 minutes.

So -/60/30 means no structural requirement, 60 minutes of integrity and 30 minutes of insulation. A -/120/30 door holds integrity for 120 minutes with the same 30 minutes of insulation.

Which fire door ratings does my building need?

The required FRL depends on the building class, where the door sits and the rating of the wall it is installed in. A door generally cannot have a lower rating than the wall around it. The National Construction Code (NCC) sets the requirement, and the approved fire safety schedule or your certifier should confirm it for each opening. The most common fire door ratings you will see on Sydney sites are -/60/30 and -/120/30, but other ratings exist, so do not assume.

Fire door ratings apply to a complete doorset

Fire door ratings apply to a tested assembly. Swapping the frame, changing the seals, cutting in a vision panel or fitting different hardware can invalidate it unless the change is covered by the test evidence. The standard that governs construction and testing is covered in our guide to AS 1905.1 fire doors.

Rating is not the same as gap or smoke performance

A door can carry the right FRL and still fail an inspection because of excessive gaps, missing seals or a closer that does not latch the door. Gap limits are covered in our gap tolerances guide. Smoke control is a separate performance requirement from fire resistance.

How to check fire door ratings on existing doors

  1. Look for the compliance label or tag, usually on the hinge edge or top of the door, and note the FRL and manufacturer.
  2. Check the frame for a matching label or marking.
  3. Compare the FRL with the fire safety schedule or building documentation.
  4. If there is no label, or it has been painted over or removed, get a qualified inspector to assess it before you assume it is compliant.

Common examples of each rating

Entry doors to apartments and other sole-occupancy units in many multi-storey residential buildings are commonly required to be -/60/30. Doors in walls with a higher fire resistance, such as some fire walls or service shafts, may need -/120/30 or another rating. These are general examples only. The rating for each opening is set by the building’s approved design, so always confirm it against the fire safety schedule rather than relying on the door type or location.

Why the rating matters at inspection time

During routine inspections and testing, a fire door is checked against the rating it is supposed to carry. A door with a missing or unreadable label, or one that no longer matches the documented FRL, is a compliance problem even if it looks sound. Keeping labels visible, avoiding paint over tags, and recording each door’s rating in your logbook makes annual checks faster. Our AS1851 compliance guide explains what building owners must keep and when inspections are due.

If a door is damaged, has been modified or cannot be matched to its documentation, treat it as unverified until a qualified person has assessed it. Repairs should use compatible, certified components so the rated system stays intact.

Frequently Asked Questions

What does -/60/30 mean on a fire door?

It means no structural adequacy requirement, 60 minutes of integrity and 30 minutes of insulation.

Is a -/120/30 door better than a -/60/30 door?

It resists fire for longer, but it is only the right choice where the opening requires it. Use the rating the NCC and your certifier specify.

Can I increase the rating of an existing door?

Not by adding components yourself. Rating comes from a tested system, so you would need a certified doorset or evidence that covers the change.

Who decides what rating a door needs?

The NCC sets the requirement and the building’s certifier or fire engineer confirms it for each opening.

Not sure what fire door ratings your doors carry? Our team can inspect, tag and report on your fire doors across Sydney. Get in touch or see our products and services.

Table Of Contents
Latest Blogs
Tags
Our Reviews
Park Sydney profile picture
Park Sydney
1 year ago
Joe has always demonstrated to be professional, reliable and detailed with his work. His broad knowledge, exceptional service and attention to detail means jobs appointed are always done to a very high level of standard. We would highly recommend utilising Joe’s experience and expertise for your building or home maintenance and repairs.
troy cohen profile picture
troy cohen
3 years ago
Comprehensive Fire Services are the specialists for Fire Door installation and rectification. Joes in depth knowledge of building codes and installation standards is an asset as when doing a job, its done right. I’ve had nothing but a positive experience with the team at CFS with them completing 500+ jobs for our business, the quality of work and attention to detail is second to none. I highly recommend there services!
Murray Allan profile picture
Murray Allan
3 years ago
Joe has helped me with several installations and repairs of fire doors and passive fire systems. He is always on time, quotes are prompt, and the work is always exceptional (especially his doors!). Would recommend his services to anyone.
George Feggaris profile picture
George Feggaris
3 years ago
I have been working with Comprehensive Fire Services since 2012, there knowledge, expertise and quality workmanship and attention to detail is amazing. Always on time, site is always left clean at the end of each job. There is no other team I would use. I would highly recommend CFS if you want the job done right. SPM Facilities Management
Greg Clayton profile picture
Greg Clayton
3 years ago
Outstanding Service Highly recommend Comprehensive Fire Services. There work is always of high quality, along with impeccable customer service.
FPAS Accreditation
FPAS Accreditation

FPAS Accreditation Number: F055161A

We are committed to delivering the highest level of professionalism and compliance in the fire protection industry. As part of this commitment, our team holds accreditation under the Fire Protection Accreditation Scheme (FPAS) — the national accreditation framework developed by Fire Protection Association Australia (FPA Australia).

Comprehensive Fire Services Office
Contact Us

Please feel free to contact us via the form below, or call our office on 0418 749 488

We respond within 2 business hours.

Newsletter

© 2026 Comprehensive Fire Services - Website by BSharp Tech